Siemens SINAMICS V90, SIMOTICS S-1FL6 Error F8501: PROFiDrive: Setpoint timeout

Industrial motor drive · taken from the manufacturer’s manual, pages cited

Fault codeF8501

PROFiDrive setpoint timeout occurred due to interrupted PROFINET connection, controller stop, or defective network. The manual's first action is: “Restore the PROFINET connection and set the controller to RUN.”

Model
Siemens SINAMICS V90, SIMOTICS S-1FL6
Display shows
PROFiDrive: Setpoint timeout (F8501)
Type
Fault code
Source
Manual p. 298

What F8501 means

PROFiDrive: Setpoint timeout p. 298

Common causes

  • The reception of setpoints from the PROFINET has been interrupted. • PROFINET connection interrupted. • Controller switched off. • Controller set into the STOP state. • PROFINET defective. p. 298

What to do

  1. Restore the PROFINET connection and set the controller to RUN. p. 298

Before you service the product, read the safety instructions in the manual p. 2.

If F8501 is still not resolved

  • Contact service / dealer for assistance p. 2
    “Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions.”
  • Contact service / dealer for assistance p. 13
    “NOTICE Property damage due to loose power connections Insufficient tightening torques or vibration can result in loose power connections. This can result in damage due to fire, device defects or malfunctions.”

This page summarises what the manufacturer’s manual says about F8501; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.