Alarm codeA7456
The actual setpoint velocity exceeds the parameterized maximum velocity limit and has been internally restricted. The manual's first action is: “Check the entered setpoint velocity.”
- Model
- Siemens SINAMICS V90, SIMOTICS S-1FL6
- Display shows
- EPOS: Setpoint velocity limited (A7456)
- Type
- Alarm code
- Source
- Manual p. 307
What A7456 means
EPOS: Setpoint velocity limited p. 307
Common causes
- The actual setpoint velocity is greater than the parameterized maximum velocity (p2571) and is therefore limited. p. 307
What to do
- Check the entered setpoint velocity. p. 307
- Reduce the velocity override. p. 307
- Increase the maximum velocity (p2571). p. 307
- Check the signal source for the externally limited velocity. p. 307
Before you service the product, read the safety instructions in the manual p. 2.
If A7456 is still not resolved
- Contact service / dealer for assistance p. 2 “Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions.”
- Contact service / dealer for assistance p. 13 “NOTICE Property damage due to loose power connections Insufficient tightening torques or vibration can result in loose power connections. This can result in damage due to fire, device defects or malfunctions.”
This page summarises what the manufacturer’s manual says about A7456; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.