Encoder feedback signal loss alarm indicates the encoder feedback signal is lost, causing the inverter to switch to sensor-less vector control mode. The manual's first action is: “Stop the inverter, then: 1. Check the encoder installation. If no encoder is installed, set 0400 = 0 and select SLVC operation mode (P1300 = 20 or 22).”
- Model
- Siemens MICROMASTER 430
- Display shows
- Encoder feedback signal loss alarm (A0590)
- Type
- Alarm code
- Source
- Manual p. 89
What A0590 means
Encoder feedback signal loss alarm p. 89
Common causes
- Feedback signal from the encoder is lost, causing the inverter to switch to sensor‑less vector control mode. p. 89
What to do
- Stop the inverter, then: 1. Check the encoder installation. If no encoder is installed, set 0400 = 0 and select SLVC operation mode (P1300 = 20 or 22). p. 89
- 2. If an encoder is installed, verify that the encoder type is correct (check the setting of parameter F0400). p. 89
- 3. Inspect the wiring between the inverter and the encoder. p. 89
- 4. Ensure the encoder is fault‑free (set P1300 = 0, run the inverter at a fixed speed, and check the encoder feedback signal in R0061). p. 89
- 5. Increase the encoder‑signal‑loss threshold value (F0492). p. 89
Before you service the product, read the safety instructions in the manual p. 7.
If A0590 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Siemens service.
This page summarises what the manufacturer’s manual says about A0590; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Siemens. Found a mistake? Report an error.