Shihlin Electric SDA Series Error AL 01: Occurred voltage (AL01)

AC servo system · taken from the manufacturer’s manual, pages cited

Alarm codeAL 01

AL01 indicates the main loop input voltage is higher than the rated permissive voltage or there's an incorrect power source system. The manual's first action is: “Screen flickers when abnormal alarm happens.”

Model
Shihlin Electric SDA Series
Display shows
Occurred voltage (AL01) (AL 01)
Type
Alarm code
Source
Manual p. 67

What AL 01 means

Occurred voltage (AL01) p. 67

Common causes

  • Occurred voltage (AL01) p. 67
  • Main loop input voltage is higher than the rated permissive voltage p. 67
  • Power source input error (incorrect power source system) p. 67
  • Actuator hardware breakdown p. 67

What to do

  1. Screen flickers when abnormal alarm happens. p. 67
  2. Power OFF→ON p. 67
  3. Press SET at the current alarm screen p. 67
  4. Alarm reset (RES) signal p. 67
  5. Use a voltmeter to measure if the main loop input voltage is within the rated permissive voltage value. Use a correct voltage source or a serial voltage stabilizer. p. 67
  6. Use a voltmeter to assess if the power source system meets the specification. Use a correct voltage source or a serial voltage stabilizer. p. 67
  7. Use a voltmeter to measure if the main loop input voltage is within the rated permissive voltage value while errors still occur. Return the machine to the agent or the factory for repairmen. p. 67

If AL 01 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Shihlin Electric service.

This page summarises what the manufacturer’s manual says about AL 01; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Shihlin Electric. Found a mistake? Report an error.