When several motors are paralleled, the inverter output exhibits a large ground‑leakage current. The manual's first action is: “• Check the motor, gain, and stability parameters.”
- Model
- Schneider Electric ATV61
- Display shows
- [Impedance Short Circuit] (SCF2)
- Type
- Error code
- Source
- Manual p. 240
What SCF2 means
[Impedance Short Circuit] p. 240
Common causes
- When several motors are paralleled, the inverter output exhibits a large ground‑leakage current. p. 240
What to do
- • Check the motor, gain, and stability parameters. p. 240
- • Add a braking resistor. p. 240
- • Verify the size of the motor / inverter / load. p. 240
- • Check the parameters of the [Frequency Table] (FqF‑) function on page 204, if this function has been enabled. p. 240
Before you service the product, read the safety instructions in the manual p. 54.
If SCF2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about SCF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.