Schneider Electric ATV61 Error SCF2: [Impedance Short Circuit]

Schneider Electric ATV61 · taken from the manufacturer’s manual, pages cited

Error codeSCF2

When several motors are paralleled, the inverter output exhibits a large ground‑leakage current. The manual's first action is: “• Check the motor, gain, and stability parameters.”

Model
Schneider Electric ATV61
Display shows
[Impedance Short Circuit] (SCF2)
Type
Error code
Source
Manual p. 240

What SCF2 means

[Impedance Short Circuit] p. 240

Common causes

  • When several motors are paralleled, the inverter output exhibits a large ground‑leakage current. p. 240

What to do

  1. • Check the motor, gain, and stability parameters. p. 240
  2. • Add a braking resistor. p. 240
  3. • Verify the size of the motor / inverter / load. p. 240
  4. • Check the parameters of the [Frequency Table] (FqF‑) function on page 204, if this function has been enabled. p. 240

Before you service the product, read the safety instructions in the manual p. 54.

If SCF2 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about SCF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.