The inverter output is shorted or grounded. The manual's first action is: “• Inspect the cable connections between the inverter and motor and check the motor’s insulation.”
- Model
- Schneider Electric ATV61
- Display shows
- [Motor Short Circuit] (SCF1)
- Type
- Error code
- Source
- Manual p. 240
What SCF1 means
[Motor Short Circuit] p. 240
Common causes
- The inverter output is shorted or grounded. p. 240
What to do
- • Inspect the cable connections between the inverter and motor and check the motor’s insulation. p. 240
- • Perform a diagnostic test via the [1.10 Diagnosis] menu. p. 240
- • Reduce the switching frequency. p. 240
- • Connect a reactor in series with the motor. p. 240
- • Check the tuning of the speed loop and braking. p. 240
Before you service the product, read the safety instructions in the manual p. 54.
If SCF1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.