Schneider Electric ATV61 Error SCF1: [Motor Short Circuit]

Schneider Electric ATV61 · taken from the manufacturer’s manual, pages cited

Error codeSCF1

The inverter output is shorted or grounded. The manual's first action is: “• Inspect the cable connections between the inverter and motor and check the motor’s insulation.”

Model
Schneider Electric ATV61
Display shows
[Motor Short Circuit] (SCF1)
Type
Error code
Source
Manual p. 240

What SCF1 means

[Motor Short Circuit] p. 240

Common causes

  • The inverter output is shorted or grounded. p. 240

What to do

  1. • Inspect the cable connections between the inverter and motor and check the motor’s insulation. p. 240
  2. • Perform a diagnostic test via the [1.10 Diagnosis] menu. p. 240
  3. • Reduce the switching frequency. p. 240
  4. • Connect a reactor in series with the motor. p. 240
  5. • Check the tuning of the speed loop and braking. p. 240

Before you service the product, read the safety instructions in the manual p. 54.

If SCF1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.