OPF2 means motor not connected or motor power is too low, output contactor is open, or motor current is momentarily unstable. The manual's first action is: “Check the connections between the inverter and motor.”
- Model
- Schneider Electric ATV61
- Display shows
- [Motor Missing Three Phases] (OPF2)
- Type
- Fault code
- Source
- Manual p. 243
What OPF2 means
[Motor Missing Three Phases] p. 243
Common causes
- Motor not connected or motor power is too low. p. 243
- Output contactor is open. p. 243
- Motor current is momentarily unstable. p. 243
What to do
- Check the connections between the inverter and motor. p. 243
- If using an output contactor, set the [Output Phase Loss Setting] (OPL) on page 193 to [Output Cut‑off] (OAC). p. 243
- For testing with a low‑power motor or without a motor: in factory‑default mode, motor phase‑loss detection is enabled, and [Output Phase Loss Setting] (OPL) = [Yes] (YES). To test or service the inverter without using a motor of the same rating (especially for high‑power inverters), disable motor phase‑loss detection by setting [Output Phase Loss Setting] (OPL) = [Not Set] (nO). p. 243
- Check and optimize the following parameters: [IR Stator Voltage Drop Compensation] (UFr) on page 21, [Motor Rated Voltage] (UnS) and [Motor Rated Current] (nCr) on page 64, and perform [Auto‑tuning] (tUn) on page 66. p. 243
Before you service the product, read the safety instructions in the manual p. 54.
If OPF2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about OPF2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.