The [4-20mA Signal Loss] code indicates an inconsistent signal on analog input A12 or a fault ignored when the [A12 Minimum Value] is not greater than 3 mA or the [A12 Type] is set to [Voltage]. The manual lists no action for this code.
- Model
- Schneider Electric ATV61
- Display shows
- [4-20mA Signal Loss] (LFL2)
- Type
- Fault code
- Source
- Manual p. 199
What LFL2 means
[4-20mA Signal Loss] p. 199
Common causes
- [Ignore Alarm](nO): Fault is ignored. This setting is only possible when the [A12 Minimum Value] (CrL2) on page 86 is not greater than 3 mA or when the [A12 Type] (A12) on page 86 is = [Voltage] (10U). p. 199
- [Free Stop](YES): Free stop. p. 199
- [Stop According to Stop Mode](Stt): Stops according to the [Stop Type] (Stt) setting on page 133; no fault is triggered. In this case the fault relay does not open, and as soon as the fault clears the inverter will be ready to restart according to the restart conditions of the active command channel (e.g., based on the [2/3 Wire Control] (tCC) and [2‑wire Type] (tCt) on page 80 if control is via terminals). To indicate the stop reason, it is recommended to assign an alarm to this fault (e.g., map it to a logic output). p. 199
- [Fall‑back Speed](LFF): Switches to the fall‑back speed and remains at that speed (t1) as long as the fault persists and the run command is not inhibited. p. 199
- [Hold Speed](rLS): When the fault occurs, the inverter holds the current speed (t1) as long as the fault remains and the run command is not cancelled. p. 199
- [Ramp Stop](rMP): Ramp stop. p. 199
- [Fast Stop](FSt): Fast stop. p. 199
- [DC Injection](dCl): DC‑injection stop. This type of stop cannot be used together with certain other functions. See the list on page 122. p. 199
- (t1) In this case, because the fault does not trigger a stop, an indication must be assigned to it via a relay or logic output. p. 199
If LFL2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about LFL2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.