The [Brake Unit Short Circuit] code indicates a short-circuit output of the brake unit, the brake unit not connected, or monitoring is required for specific inverter models without a resistor or brake unit. The manual's first action is: “Check the wiring of the brake unit and resistor.”
- Model
- Schneider Electric ATV61
- Display shows
- [Brake Unit Short Circuit] (bUF)
- Type
- Fault code
- Source
- Manual p. 239
What bUF means
[Brake Unit Short Circuit] p. 239
Common causes
- Short‑circuit output of the brake unit. p. 239
- Brake unit not connected. p. 239
- For ATV61HeeM3X inverters of 55 kW (75 HP) and above, and ATV61HeeM4 inverters of 90 kW (120 HP) and above, if the inverter is not equipped with a resistor or brake unit, monitoring of this fault must be disabled via the [Brake Resistor Fault Management] (bUb) parameter on page 205. p. 239
What to do
- Check the wiring of the brake unit and resistor. p. 239
- Inspect the brake resistor. p. 239
- Turn the inverter off and then on again. p. 239
- Check internal connections. p. 239
- Inspect/repair the inverter. p. 239
Before you service the product, read the safety instructions in the manual p. 54.
If bUF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about bUF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.