The [IGBT De‑saturation] code indicates an inverter output short circuit or ground fault. The manual's first action is: “Check the cable connections between the inverter and motor and verify the motor insulation.”
- Model
- Schneider Electric ATV61
- Display shows
- [IGBT De‑saturation] (HdF)
- Type
- Fault code
- Source
- Manual p. 239
What HdF means
[IGBT De‑saturation] p. 239
Common causes
- Inverter output short circuit or ground fault. p. 239
What to do
- Check the cable connections between the inverter and motor and verify the motor insulation. p. 239
- Perform a diagnostic test via the [1.10 Diagnosis] menu. p. 239
Before you service the product, read the safety instructions in the manual p. 54.
If HdF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about HdF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.