The [Damper Open] code indicates the damper remains open despite meeting closing conditions. The manual's first action is: “Inspect the damper and its wiring.”
- Model
- Schneider Electric ATV61
- Display shows
- [Damper Open] (Fd2)
- Type
- Error code
- Source
- Manual p. 239
What Fd2 means
[Damper Open] p. 239
Common causes
- Although the closing conditions are met, the damper remains open. p. 239
What to do
- Inspect the damper and its wiring. p. 239
- Check the feedback circuit. p. 239
- Check the function delay, see page 172. p. 239
Before you service the product, read the safety instructions in the manual p. 54.
If Fd2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about Fd2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.