Motor Overload means approximately 120 seconds after the fault is detected, or approximately 120 seconds after the fault occurs, or parameter [Motor Control Mode] (P1) is set incorrectly. The manual's first action is: “Select the correct setting value for parameter [Motor Control Mode] (P1).”
- Model
- Schneider Electric ATV212
- Display shows
- (Motor Overload) (OL2)
- Type
- Fault code
- Source
- Manual p. 51
What OL2 means
(Motor Overload) p. 154
Common causes
- Approximately 120 seconds after the fault is detected p. 154
- Approximately 120 seconds after the fault occurs p. 154
- Parameter [Motor Control Mode] (P1) is set incorrectly. p. 154
- Motor is blocked. p. 154
- Continuous low‑speed operation. p. 154
- Load applied to the motor is too large. p. 154
What to do
- Select the correct setting value for parameter [Motor Control Mode] (P1). p. 154
- Check the load. p. 154
- Adjust parameter OL1N to the overload level the motor can tolerate during low‑speed operation. p. 154
Before you service the product, read the safety instructions in the manual p. 5.
If OL2 is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about OL2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.