Fault codeOL1
Inverter Overload means approximately 30 seconds after the fault is detected, or approximately 30 seconds after the fault occurs, or acceleration time is too short. The manual's first action is: “Increase the acceleration time parameter (RCC or F500).”
- Model
- Schneider Electric ATV212
- Display shows
- (Inverter Overload) (OL1)
- Type
- Fault code
- Source
- Manual p. 51
What OL1 means
(Inverter Overload) p. 154
Common causes
- Approximately 30 seconds after the fault is detected p. 154
- Approximately 30 seconds after the fault occurs p. 154
- Acceleration time is too short. p. 154
- DC injection current level is too high. p. 154
- Parameter [Motor Control Mode] (P1) is set incorrectly. p. 154
- The inverter is starting a rotating load. p. 154
- Load is too large. p. 154
- Using an inverter with a higher rated power. p. 154
What to do
- Increase the acceleration time parameter (RCC or F500). p. 154
- Decrease the setting of parameter F251 and/or F252. p. 154
- Select the correct setting for parameter [Motor Control Mode] (P1). p. 154
- Enable flywheel start, parameter F301. p. 154
- Set parameter F302 to 2. p. 154
- Use an inverter with a higher rated power. p. 154
Before you service the product, read the safety instructions in the manual p. 5.
If OL1 is still not resolved
- 与当地的 Schneider Electric 代表联系 p. 7 “如果直流总线电容未完全放电,请与当地的 Schneider Electric 代表联系”
This page summarises what the manufacturer’s manual says about OL1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.
