Error codeOP1
OP1 indicates input voltage fluctuation, voltage capacity of 200 kA or higher, or a power-factor correction capacitor switch requesting closure. The manual's first action is: “Install a suitable input reactor.”
- Model
- Schneider Electric ATV 21
- Display shows
- 000A (OP1)
- Type
- Error code
- Source
- Manual p. 234
What OP1 means
000A p. 234
Common causes
- Input voltage fluctuates abnormally. p. 234
- (1) Voltage capacity is 200 kA or higher. p. 234
- (2) A power‑factor correction capacitor switch requests closure. p. 234
- (3) A thyristor‑based system is connected on the same power‑distribution line. p. 234
- After a short stop, a restart signal is applied to a stationary motor. p. 234
What to do
- Install a suitable input reactor. p. 234
- Use F3G1 (automatic restart) and F3G2 (high‑performance control). p. 234
Before you service the product, read the safety instructions in the manual p. 8.
If OP1 is still not resolved
This page summarises what the manufacturer’s manual says about OP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.