Schneider Electric ATV 21 Error OP1: 000A

Schneider Electric ATV 21 Frequency Transformer · taken from the manufacturer’s manual, pages cited

Error codeOP1

OP1 indicates input voltage fluctuation, voltage capacity of 200 kA or higher, or a power-factor correction capacitor switch requesting closure. The manual's first action is: “Install a suitable input reactor.”

Model
Schneider Electric ATV 21
Display shows
000A (OP1)
Type
Error code
Source
Manual p. 234

What OP1 means

000A p. 234

Common causes

  • Input voltage fluctuates abnormally. p. 234
  • (1) Voltage capacity is 200 kA or higher. p. 234
  • (2) A power‑factor correction capacitor switch requests closure. p. 234
  • (3) A thyristor‑based system is connected on the same power‑distribution line. p. 234
  • After a short stop, a restart signal is applied to a stationary motor. p. 234

What to do

  1. Install a suitable input reactor. p. 234
  2. Use F3G1 (automatic restart) and F3G2 (high‑performance control). p. 234

Before you service the product, read the safety instructions in the manual p. 8.

If OP1 is still not resolved

  • Contact local sales agent for parts replacement. p. 7
    “如要更换零件,请致电当地的销售代理处”
  • Perform daily equipment inspection. p. 7
    “应每天对设备进行检查”

This page summarises what the manufacturer’s manual says about OP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.