Schneider Electric Altivar 71W/E5 Error F 1: [EXTERNAL FAULT [1 7 Bit]

Schneider Electric Altivar 71W/E5 · taken from the manufacturer’s manual, pages cited

Fault codeF 1

The F 1 code indicates an external fault [1 7 Bit] triggered by an external device depending on user, loss of one phase at drive output, or overheating of the PTC1 probes detected. The manual's first action is: “Check the device which has caused the fault and reset the drive”

Model
Schneider Electric Altivar 71W/E5
Display shows
[EXTERNAL FAULT [1 7 Bit] (F 1)
Type
Fault code
Source
Manual p. 77

What F 1 means

[EXTERNAL FAULT [1 7 Bit] p. 77

Common causes

  • Fault triggered by an external device, depending on user p. 77
  • Loss of one phase at drive output p. 77
  • Overheating of the PTC1 probes detected p. 77
  • PTC1 probes open or short-circuited p. 77
  • Interruption in communication on the Modbus bus p. 77

What to do

  1. Check the device which has caused the fault and reset the drive p. 77
  2. Check the connections from the drive to the motor p. 77
  3. Check the motor load and motor size p. 77
  4. Check the motor ventilation p. 77
  5. Wait for the motor to cool before restarting p. 77
  6. Check the type and state of the PTC probes p. 77
  7. Check the PTC probes and the wiring between them and the motor/drive p. 77
  8. Check the communication bus p. 77
  9. Check the time-out p. 77
  10. Consult the Modbus manual p. 77

Before you service the product, read the safety instructions in the manual p. 43.

If F 1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about F 1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.