Schneider Electric Altivar 71 Error SPF: [Speed fdback loss]

Schneider Electric Altivar 71 · taken from the manufacturer’s manual, pages cited

Fault codeSPF

Speed fdback loss means no resolver or encoder feedback signal, no Top Z signal after activation, or no signal on pulse input. The manual's first action is: “Check the wiring between the encoder or resolver and the drive.”

Model
Schneider Electric Altivar 71
Display shows
[Speed fdback loss] (SPF)
Type
Fault code
Source
Manual p. 289

What SPF means

[Speed fdback loss] p. 289

Common causes

  • No resolver or encoder feedback signal p. 289
  • No Top Z signal after the activation of the Top Z function and 2 cycles. p. 289
  • No signal on "Pulse input", if the input is used for speed measurement p. 289

What to do

  1. Check the wiring between the encoder or resolver and the drive. p. 289
  2. Check the encoder or resolver. p. 289
  3. Check all the configuration parameters for the encoder used. p. 289
  4. Refer to the [1.10 DIAGNOSTICS] menu for the value of parameter RESE. p. 289
  5. Check the wiring of the input cable and the detector used. p. 289

Before you service the product, read the safety instructions in the manual p. 16.

If SPF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about SPF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.