Schneider Electric Altivar 71 Error OCF: [Overcurrent]

Schneider Electric Altivar 71 · taken from the manufacturer’s manual, pages cited

Fault codeOCF

Parameters in the [SETTINGS] (SET-) and [1.4 MOTOR CONTROL] (drC-) menus are not correct indicates incorrect parameters in the [SETTINGS] and [1.4 MOTOR CONTROL] menus. The manual's first action is: “Check the parameters.”

Model
Schneider Electric Altivar 71
Display shows
[Overcurrent] (OCF)
Type
Fault code
Source
Manual p. 289

What OCF means

[Overcurrent] p. 289

Common causes

  • Parameters in the [SETTINGS] (SET-) and [1.4 MOTOR CONTROL] (drC-) menus are not correct. p. 289
  • Inertia or load too high p. 289
  • Mechanical locking p. 289

What to do

  1. Check the parameters. p. 289
  2. Check the size of the motor/drive/load. p. 289
  3. Check the state of the mechanism. p. 289

Before you service the product, read the safety instructions in the manual p. 16.

If OCF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about OCF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.