There is a short-circuit or grounding at the drive output. The manual's first action is: “Check the cables connecting the drive to the motor, and the motor insulation. Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu. Reduce the switching frequency. Connect chokes in series with the motor.”
- Model
- Schneider Electric Altivar 61
- Display shows
- [Motor short circuit] (SCF1)
- Type
- Fault code
- Source
- Manual p. 54
What SCF1 means
[Motor short circuit] p. 54
Common causes
- Short-circuit or grounding at the drive output p. 54
What to do
- Check the cables connecting the drive to the motor, and the motor insulation. Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu. Reduce the switching frequency. Connect chokes in series with the motor. p. 54
Before you service the product, read the safety instructions in the manual p. 33.
If SCF1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.