The code SCF indicates a short-circuit or earthing at the drive output or significant earth leakage current if multiple motors are connected in parallel. The manual's first action is: “Check the cables connecting the drive to the motor, and the motor insulation.”
- Model
- Schneider Electric Altivar 31
- Display shows
- motor short-circuit (SCF)
- Type
- Fault code
- Source
- Manual p. 42
What SCF means
motor short-circuit p. 42
Common causes
- Short-circuit or earthing at the drive output p. 42
- Significant earth leakage current at the drive output if several motors are connected in parallel p. 42
What to do
- Check the cables connecting the drive to the motor, and the motor insulation. p. 42
- Reduce the switching frequency. p. 42
- Connect chokes in series with the motor. p. 42
If SCF is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.
This page summarises what the manufacturer’s manual says about SCF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.