Schneider Electric Altistart 48 Error PHF

Altistart 48 soft starter · taken from the manufacturer’s manual, pages cited

Fault codePHF

Loss of a line phase or Loss of a motor phase means a phase is missing in the line or motor connection. The manual's first action is: “Check the line, the connection to the starter and any isolating devices located between the line and the starter (contactor, fuses, circuit-breaker, etc.).”

Model
Schneider Electric Altistart 48
Display shows
PHF
Type
Fault code
Source
Manual p. 159

What PHF means

Loss of a line phase p. 159

Common causes

What to do

  1. Check the line, the connection to the starter and any isolating devices located between the line and the starter (contactor, fuses, circuit-breaker, etc.). p. 159
  2. Check the motor connection and any isolating devices located between the starter and the motor (contactors, circuit-breakers, etc.). Check the motor state. Check that the configuration of the PHL parameter is compatible with the motor used. p. 159

If PHF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about PHF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.