Schneider Electric Altistart 48 Error OCF

Altistart 48 soft starter · taken from the manufacturer’s manual, pages cited

Fault codeOCF

Overcurrent indicates a short-circuit on starter output, internal short-circuit, bypass contactor stuck, or overrate starter. The manual's first action is: “Switch the starter off. - Check the connecting cables and the motor isolation - Check the thyristors - Check the bypass contactor (contact stuck) - Check the parameter value bSt in the menu drC page 139”

Model
Schneider Electric Altistart 48
Display shows
OCF
Type
Fault code
Source
Manual p. 157

What OCF means

Overcurrent: - impeding short-circuit on starter output - internal short-circuit - bypass contactor stuck - overrate starter p. 157

Common causes

  • Overcurrent: - impeding short-circuit on starter output - internal short-circuit - bypass contactor stuck - overrate starter p. 157

What to do

  1. Switch the starter off. - Check the connecting cables and the motor isolation - Check the thyristors - Check the bypass contactor (contact stuck) - Check the parameter value bSt in the menu drC page 139 p. 157

If OCF is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Schneider Electric service.

This page summarises what the manufacturer’s manual says about OCF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider Electric. Found a mistake? Report an error.