An expansion I/O module could not communicate at the baud rate that is specified in the user program I/O configuration, or The number of input or output image words that are configured in the user program exceeds the image size in the expansion I/O module. The manual's first action is: “Change the baud rate in the user program I/O configuration, and Recompile, reload the program and enter the Run mode, or Replace the module.”
- Model
- Rockwell Automation MicroLogix 1400
- Display shows
- EXPANSION I/O MODULE BAUD RATE ERROR (xx8f(1))
- Type
- Error code
- Source
- Manual p. 405
What xx8f(1) means
EXPANSION I/O MODULE BAUD RATE ERROR p. 405
Common causes
- An expansion I/O module could not communicate at the baud rate that is specified in the user program I/O configuration. p. 405
- The number of input or output image words that are configured in the user program exceeds the image size in the expansion I/O module. p. 405
What to do
- Change the baud rate in the user program I/O configuration, and Recompile, reload the program and enter the Run mode, or Replace the module. p. 405
- Correct the user program I/O configuration to reduce the number of input or output words, and Recompile, reload the program, and enter the Run mode. p. 405
Before you service the product, read the safety instructions in the manual p. 274.
If xx8f(1) is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Rockwell Automation service.
This page summarises what the manufacturer’s manual says about xx8f(1); each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Rockwell Automation. Found a mistake? Report an error.