Current limiting controller is active. The manual's first action is: “Check for and correct: • Excessive motor load. • In sufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). • Faulty…
Parameter values for the user load curve are inconsistent. The manual's first action is: “Check that the following conditions are met: • 3704 LOAD FREQ 1 ≤ 3707 LOAD FREQ 2 ≤ 3710 LOAD FREQ 3 ≤ 3713 LOAD FREQ 4 ≤ 3716…
PAR PFC IO 3 indicates insufficient digital inputs allocated for each PFC motor. The manual lists no action for this code.
PAR PFC IO 2 indicates mismatch between number of PFC motors and configured relay outputs. The manual lists no action for this code.
PAR PFC IO 1 indicates incomplete I/O configuration for PFC with relay conflicts. The manual lists no action for this code.
PAR PCU 1 indicates inconsistent power control parameters due to improper motor nominal frequency or speed. The manual's first action is: “Check for both of the following: • 1 ≤ (60 · 9907 MOTOR NOM FREQ / 9908 MOTOR …
PAR PFC MODE indicates an inconsistency in power factor correction mode settings. The manual lists no action for this code.
PAR FIELDBUS MISSING indicates a missing fieldbus connection when fieldbus control is enabled. The manual's first action is: “Check for and correct: • A parameter is set to fieldbus control (e.g. 1001 EXT1 COMMANDS = …
PAR EXT RO indicates inconsistent parameter values related to extension relay module configuration. The manual's first action is: “Check for the following: • Extension relay module not connected and • 1410...1412 RELA…
PAR PCU 2 indicates inconsistent power control parameters due to improper motor nominal kVA or power. The manual's first action is: “Check for the following: • 1.1 ≤ (9906 MOTOR NOM CURR · 9905 MOTOR NOM VOLT · 1.73 /…
PAR AO SCALE indicates inconsistent parameter values for analog output scaling. The manual's first action is: “Check for any of the following: • 1504 MINIMUM AO1 > 1505 MAXIMUM AO1. • 1510 MINIMUM AO2 > 1511 MAXIMUM A…
PAR AI SCALE indicates inconsistent parameter values for analog input scaling. The manual's first action is: “Check for any of the following: • 1301 MINIMUM A1 > 1302 MAXIMUM A1. • 1304 MINIMUM A2 > 1305 MAXIMUM A2.”
Reserved (obsolete) is an obsolete code with no current meaning. The manual lists no action for this code.
PAR PFC REF NEG indicates a negative reference value when PFC is enabled. The manual's first action is: “Check for the following: • 2007 MINIMUM FREQ is negative, when 8123 PFC ENABLE is active.”
PAR HZRP M indicates inconsistent parameter values related to frequency and speed settings. The manual's first action is: “Check for any of the following: • 2001 MINIMUM SPEED > 2002 MAXIMUM SPEED. • 2007 MINIMUM FREQ…