Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. The manual's first action is: “To control automatic reset, use Group 31: AUTOMATIC RESET.”
Motor is operating in the stall region. This alarm warns that a MOTOR STALL fault trip may be near. The manual lists no action for this code.
Not used. The manual lists no action for this code.
Motor is hot, based on either the drive's estimate or on temperature feedback. This alarm warns that a MOT OVERTEMP fault trip may be near. The manual's first action is: “Check: • Check for overloaded motor. • Adjust …
Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault may be near. The manual's first action is: “Check for and correct: • Fan failure. • Obstructions in the air flow. • Dirt or dust coating on the heat…
Panel communication is lost and either: drive is in local control mode (the control panel displays LOC), or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction. The manual's firs…
Analog input 2 is lost, or value is less than the minimum setting. The manual's first action is: “Check: • Input source and connections. • Parameter that sets the minimum (3022). • Parameter that sets the alarm/fault …
Analog input 1 is lost, or value is less than the minimum setting. The manual's first action is: “Check: • Input source and connections. • Parameter that sets the minimum (3021). • Parameter that sets the alarm/fault …
Fieldbus communication has timed out. The manual's first action is: “Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51: EXT COMM MODULE or Group 5…
The change in direction being attempted is not allowed. The manual's first action is: “Either: • Do not attempt to change the direction of motor rotation, or • Change parameter 1003 DIRECTION to allow direction change…
Undervoltage controller is active. The manual's first action is: “Check for and correct: • Undervoltage on mains.”
Overvoltage controller is active. The manual's first action is: “Check for and correct: • Static or transient overvoltages in the input power supply. • Insufficient deceleration time (parameters 2203 DECELER TIME 1 an…
Current limiting controller is active. The manual's first action is: “Check for and correct: • Excessive motor load. • In sufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). • Faulty…
Parameter values for the user load curve are inconsistent. The manual's first action is: “Check that the following conditions are met: • 3704 LOAD FREQ 1 ≤ 3707 LOAD FREQ 2 ≤ 3710 LOAD FREQ 3 ≤ 3713 LOAD FREQ 4 ≤ 3716…
PAR PFC IO 3 indicates insufficient digital inputs allocated for each PFC motor. The manual lists no action for this code.