This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. The manual's first action is: “To control PID sleep, use parameters 4022...4026 or …
This alarm warns that the PFC interlocks are active, which means that the drive cannot start the following: any motor (when Autochange is used). The speed regulated motor (when Autochange is not u The manual lists no …
This alarm warns that the PFC autochange function is active. The manual's first action is: “To control PFC, use Group 81: PFC CONTROL and the PFC macro on page 84.”
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. The manual's first action is: “To control automatic reset, use Group 31: AUTOMATIC RESET.”
Motor is operating in the stall region. This alarm warns that a MOTOR STALL fault trip may be near. The manual lists no action for this code.
Not used. The manual lists no action for this code.
Motor is hot, based on either the drive's estimate or on temperature feedback. This alarm warns that a MOT OVERTEMP fault trip may be near. The manual's first action is: “Check: • Check for overloaded motor. • Adjust …
Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault may be near. The manual's first action is: “Check for and correct: • Fan failure. • Obstructions in the air flow. • Dirt or dust coating on the heat…
Panel communication is lost and either: drive is in local control mode (the control panel displays LOC), or drive is in remote control mode (REM) and is parameterized to accept start/stop, direction. The manual's firs…
Analog input 2 is lost, or value is less than the minimum setting. The manual's first action is: “Check: • Input source and connections. • Parameter that sets the minimum (3022). • Parameter that sets the alarm/fault …
Analog input 1 is lost, or value is less than the minimum setting. The manual's first action is: “Check: • Input source and connections. • Parameter that sets the minimum (3021). • Parameter that sets the alarm/fault …
Fieldbus communication has timed out. The manual's first action is: “Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51: EXT COMM MODULE or Group 5…
The change in direction being attempted is not allowed. The manual's first action is: “Either: • Do not attempt to change the direction of motor rotation, or • Change parameter 1003 DIRECTION to allow direction change…
Undervoltage controller is active. The manual's first action is: “Check for and correct: • Undervoltage on mains.”
Overvoltage controller is active. The manual's first action is: “Check for and correct: • Static or transient overvoltages in the input power supply. • Insufficient deceleration time (parameters 2203 DECELER TIME 1 an…