Time-out from I/Os due to referencing a nonexistent module or unacknowledged I/O module. The manual's first action is: “Correct the program error or replace the I/O module.”
Power failure occurred, causing system interruption. The manual lists no action for this code.
Block stack overflow because maximum nesting depth of 16 (or 32 for CPU 944) has been exceeded. The manual's first action is: “Correct the program error.”
Statement cannot be interpreted in the S5-115U due to decoding failure or parameter exceedance. The manual's first action is: “Correct the program error.”
Operation interrupted by a programmer STOP request or programmed STOP statements. The manual lists no action for this code.
Transfer error for data blocks because the data word number exceeds the data block length or DB not opened. The manual's first action is: “Correct the program error.”
Substitution error due to incorrect actual parameter passed to a function block. The manual's first action is: “Correct the function block call.”
Interrupt display word indicating mode selector is on STOP. The manual's first action is: “Put the mode selector on RUN.”
I/Os not ready because of power failure, interrupted connection, or no terminator in the central controller. The manual's first action is: “• Check the power supply in the expansion unit. • Check the connection. • Ins…
No terminator in the central controller due to missing or low battery requiring replacement and reset. The manual's first action is: “Replace the battery. Perform an Overall Reset. Reload the program.”
The submodule ID is illegal because an AG 110S/135U/15DU submodule was incorrectly installed. The manual's first action is: “Plug in the correct submodule.”
Error in the CPU self-test routine indicating a hardware fault requiring CPU replacement. The manual's first action is: “Replace the CPU.”
Interprocessor communication flag transfer list is incorrect due to DB1 programming error. The manual's first action is: “Check the following: • ID for interprocessor communication flag definitions ("MASK01")(see Sect…
Faulty block caused by power failure or interrupted block transfer between programmer and PLC. The manual's first action is: “Perform an Overall Reset. Reload the program.”
Faulty block caused by power failure or interrupted block transfer between programmer and PLC. The manual's first action is: “Perform an Overall Reset. Reload the program.”