Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
DNP3 10K events are enabled along with Recipe/Data Log in user program. The manual's first action is: “['Remove Recipe/Data Log configuration when DNP3 10K events bit (S:36/11) is set, then reload and Run.', 'OR', 'Cl…
An indirect address reference in the ladder program is outside of the entire data file space. The manual's first action is: “['Correct the program to ensure that there are no indirect references outside the data file …
A fault routine number was entered in the status file, number (S:29), but either the fault routine was not physically created, or the fault routine number was less than 3 or greater than 255. The manual's first action…
An error occurred in the STI configuration. The manual's first action is: “See the Error Code in the STI Function File for the specific error.”
The program scan time exceeded the watchdog timeout value (S:3H). The manual's first action is: “['Determine if the program is caught in a loop and correct the problem.', 'Increase the watchdog timeout value in the st…
A minor bit fault (bits 0,...7) in S:5 was set at the end of scan. The manual's first action is: “['Correct the instruction logic causing the error.', 'Enter the status file display in your programming software and cl…
User program is incompatible with OS at power-up. The manual's first action is: “['Upgrade the OS using ControlFLASH.', 'Contact your local Rockwell Automation representative for more information about available opera…
User program in memory module is incompatible with the operating system. The manual's first action is: “['Upgrade the OS using ControlFLASH to be compatible with the memory module.', 'Obtain a new memory module.', 'Co…
Memory module user program does not match controller user program, as indicated by bit S:2/9 being set. The manual's first action is: “Transfer the memory module program to the controller and then change to Run mode.”
User fault routine executed at power-up and bit S:1/3 was not cleared after the routine. The manual's first action is: “• Either reset bit S:1/3 if this is consistent with the application requirements, and change the …
User program I/O configuration file is invalid. The manual's first action is: “Recompile and reload the program, and enter the Run mode. If the error persists, be sure to use RSI programming software to develop and lo…
Ladder program has a memory integrity problem. The manual's first action is: “• Reload the program or recompile and reload the program. If the error persists, be sure to use RSI programming software to develop and loa…
Ladder File 2 is missing from the program. The manual's first action is: “• Recompile and reload the program.”
Base hardware has faulted or is incompatible with the operating system. The manual's first action is: “• Upgrade the OS using ControlFLASH. • Replace the Controller. • Contact your local Rockwell Automation representa…
Operating system required for the user program is missing or corrupt. The manual's first action is: “• Download a new OS using ControlFLASH™. • Contact your local Rockwell Automation representative for more informatio…