The check is wrong when EEPROM is read in the absolute encoder means PA1 parameter setting is wrong, or when power on the data check is wrong after the drive unit reads EEPROM. The manual's first action is: “Call the …
Reading EEPROM in the absolute encoder is wrong means PA1 parameter setting is wrong, or when power on the drive unit reading the encoder EEPROM is wrong, or the motor's encoder EEPROM is damaged. The manual's first a…
For the absolute encoder, the read data is wrong in sensor mode means PA1 parameter setting is wrong, or the encoder feedback CN2 is disconnected or its connection is not stable, or the absolute encoder is damaged. Th…
Alarm occurs when the temperature is higher than 75°C means the motor overload running for a long time, or the environmental temperature is too high, or the servo drive unit is damaged. The manual's first action is: “…
Alarm occurs when the temperature of radiator is below -20°C means the environmental temperature is too low. The manual's first action is: “Improve the environmental temperature.”
Three-phase main power down means 3-phase main power supply is power down or drops instantly, or three-phase main power detection circuit is faulty. The manual's first action is: “Check the main power, ensure the powe…
The external brake pipe is fault means PA225 setting is wrong or the brake pipe is damaged. The manual's first action is: “Set correctly PA225”
Excessive pulse electronic gear ratio means the setting of gear ratio is inappropriate. The manual's first action is: “Re-set parameter PA29/PA30 correctly.”
The power supply charge is fault means the charge circuit is damaged. The manual's first action is: “Change the drive unit.”
Encoder UVW signals are illegal codes means the interface connection is not stable or the cable shield is bad, or the encoder UVW signals are damaged, or the encoder's interface circuit is fault. The manual's first ac…
Excessive AC input voltage alarm means the three-phase AC power input voltage exceeds 115% of the rated voltage. The manual's first action is: “Adjust the grid voltage or increase some power-stabilizing devices such a…
Parameter error detected after power-on due to conflict during software upgrading. The manual's first action is: “Re-write the parameter and turn on the power again.”
Software upgrading parameter error occurs when parameters are not modified and saved after software recording or upgrading. The manual's first action is: “Restore the default parameters and re-power on after the param…
Current sample is wrong due to abnormal working voltage or damage in current sensor, sample circuit, or sample resistance. The manual's first action is: “Change the drive unit.”
Open phase of power supply alarms occur when 3-phase input power supply is missing one phase. The manual's first action is: “Check the input power supply.”