Feedback loss (FBE) means abnormal wiring of the feedback circuit, a faulty feedback sensor, or the minimum current specification of the input signal does not match. The manual's first action is: “→ Verify whether the cable is broken or wired incorrectly and correct it”
- Model
- Omron SYSDRIVE 3G3MZ
- Display shows
- Feedback loss (FBE) (FBE)
- Type
- Fault code
- Source
- Manual p. 170
What FBE means
Feedback loss (FBE) p. 170
Common causes
- Abnormal wiring of the feedback circuit p. 170
- Faulty feedback sensor p. 170
- Minimum current specification of the input signal does not match p. 170
- Setting the feedback loss detection time (nA.08) to “0.0”, rendering it ineffective p. 170
What to do
- → Verify whether the cable is broken or wired incorrectly and correct it p. 170
- → Check the sensor condition; if damaged, replace the sensor p. 170
- → Set the minimum current input of multifunction analog input A2 (n4.15) to a value that matches the input signal p. 170
Before you service the product, read the safety instructions in the manual p. 170.
If FBE is still not resolved
- contact service or dealer p. 170 “警告发生时,请根据下表来检测原因,采取妥当的措施”