Mitsubishi Electric MDS-C1 Series Error 2F: Motor side detector, communication error

AC Servo/Spindle · taken from the manufacturer’s manual, pages cited

Error code2F

A communication error occurred between the motor end detector or linear scale and the drive unit, possibly due to disconnections or cable interference. The manual's first action is: “PR”

Model
Mitsubishi Electric MDS-C1 Series
Display shows
Motor side detector, communication error (2F)
Type
Error code
Source
Manual p. 310

What 2F means

Motor side detector, communication error p. 310

Common causes

  • A communication data error was detected with the motor end detector or linear scale in the linear servo. Or, communication was cut off. p. 310
  • Check whether the drive unit connectors (CN2) or detector connectors are disconnected. p. 310
  • Is the detector cable wired in the same conduit as the motor's power cable or are the two cables laid in parallel near each other? p. 310
  • Is the motor FG wire connected only to the drive unit which drives it? (Is the motor grounded to one point?) p. 310
  • Turn the power OFF, and check the detector cable connection with a tester. (Is the cable shielded?) p. 310
  • Connect to another normal axis drive unit, and check whether the fault is on the drive unit side or detector side. p. 310
  • Check if there is any abnormality in the detector's ambient environment. (Ex. Ambient temperature, noise, grounding) p. 310

What to do

  1. PR p. 310
  2. The connector is disconnected (or loose). Correctly install. p. 310
  3. The cables are wired near each other. (Noise is entering from the power cable.) Improve the cable wiring. p. 310
  4. The motor FG wire is grounded on the motor side. Connect together on the drive unit side. p. 310
  5. There is a connection fault. Replace the detector cable. p. 310
  6. The alarm is on the drive unit side. Replace the drive unit. p. 310
  7. No abnormality is found in particular. Replace the detector. (With the absolute position system, the zero point must be established.) p. 310

Before you service the product, read the safety instructions in the manual p. 4.

If 2F is still not resolved

  • contact service / dealer p. 5
    “Wiring, maintenance and inspection work must be done by a qualified technician.”

This page summarises what the manufacturer’s manual says about 2F; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Mitsubishi Electric. Found a mistake? Report an error.