Over-current when acceleration means excessive current during acceleration, possibly due to short-circuit, heavy load, or unsuitable V/F curve. The manual's first action is: “1. Inspect whether motor damaged, insulation worn or cable damaged.”
- Model
- Invt Electric CHV100
- Display shows
- Over-current when acceleration (OC1)
- Type
- Fault code
- Source
- Manual p. 112
What OC1 means
Over-current when acceleration p. 112
Common causes
- 1. Short-circuit or ground fault occurred at inverter output. p. 112
- 2. Load is too heavy or Acc/Dec time is too short. p. 112
- 3. V/F curve is not suitable. p. 112
- 4. Sudden change of load. p. 112
What to do
- 1. Inspect whether motor damaged, insulation worn or cable damaged. p. 112
- 2. Increase Acc/Dec time or select bigger capacity inverter. p. 112
- 3. Check and adjust V/F curve. p. 112
- 4. Check the load. p. 112
If OC1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Invt Electric service.
This page summarises what the manufacturer’s manual says about OC1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Invt Electric. Found a mistake? Report an error.