Application fault– Magnetic pole check failed happens due to incorrect power cable phase sequence or conflicting encoder direction during magnetic pole verification. The manual's first action is: “1. Ensure power cable connection is correct.”
- Model
- INVT DA180
- Display shows
- Application fault– Magnetic pole check failed (Er25-8)
- Type
- Fault code
- Source
- Manual p. 275
What Er25-8 means
Application fault– Magnetic pole check failed p. 275
Common causes
- 1. The power cable phase sequence is incorrect. p. 275
- 2. The encoder direction conflicts with the power cable phase sequence. p. 275
- 3. External force or overload occurs in the check. p. 275
What to do
- 1. Ensure power cable connection is correct. p. 275
- 2. Ensure encoder settings are correct. p. 275
- 3. Eliminate the condition that causes the external force. p. 275
If Er25-8 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact INVT service.
This page summarises what the manufacturer’s manual says about Er25-8; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with INVT. Found a mistake? Report an error.