Fault codeEr13-1
Main circuit undervoltage occurs when the DC voltage is too low, possibly due to low grid voltage or an open buffer relay. The manual's first action is: “3120-0D01h”
- Model
- INVT DA180
- Display shows
- Main circuit undervoltage (Er13-1)
- Type
- Fault code
- Source
- Manual p. 258
What Er13-1 means
Main circuit undervoltage p. 258
Common causes
- The DC voltage of the drive main circuit is higher than the specified voltage. p. 258
- 1. The grid voltage is too low. p. 258
- 2. The buffer relay is not closed. p. 258
- 3. The drive output power is too high. p. 258
- 4. The internal DC voltage detection circuit of the drive is damaged. p. 258
What to do
- 3120-0D01h p. 258
- 1. Ensure the grid input voltage is within the allowed range. 2. Repower on the drive. Ensure the buffer relay is closed. If the buffer relay is closed, there is a sound indicating actuation. p. 258
- 3. Check R0.07 when the drive is disabled. If it is abnormal and does not match the grid input voltage, replace the drive. p. 258
If Er13-1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact INVT service.
This page summarises what the manufacturer’s manual says about Er13-1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with INVT. Found a mistake? Report an error.