AT failed to complete normally because the process variable (S4) fluctuated excessively, which stops AT due to AT execution error. The manual's first action is: “AT is stopped because of AT execution error.”
- Model
- IDEC OpenNet Controller
- Display shows
- 201
- Type
- Error code
- Source
- Manual p. 4
What 201 means
AT failed to complete normally because the process variable (S4) fluctuated excessively. To restart AT, set the AT sampling period (S1+19) or the input filter coefficient (S1+11) to a larger value. p. 4
What to do
- AT is stopped because of AT execution error. p. 4
If 201 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact IDEC service.