IDEC OpenNet Controller Error Codes

10 codes from page 4 of the manual

This is the list of error codes the IDEC manual gives for the OpenNet Controller IDEC OpenNet Controller. Find your code below and open it for what the manual says about its causes and what to do.

Error codes from p. 4

CodeWhat it meansPage
100 The operation mode (S1+3) is set to a value over 2. p. 4
101 The linear conversion (S1+4) is set to a value over 1. p. 4
102 When the linear conversion is enabled (S1+4 set to 1), the linear conversion maximum value (S1+5) and the linear conversion minimum value (S1+6) are set to the same value. p. 4
103 The output manipulated variable upper limit (S1+16) is set to a value smaller than the output manipulated variable lower limit (S1+17). p. 4
104 When the linear conversion is enabled (S1+4 set to 1), the AT set point (S1+21) is set to a value larger than the linear conversion maximum value (S1+5) or smaller than the linear conversion minimum value (S1+6). p. 4
105 When the linear conversion is disabled (S1+4 set to 0), the AT set point (S1+21) is set to a value larger than 4000. p. 4
106 When the linear conversion is enabled (S1+4 set to 1), the set point (S3) is set to a value larger than the linear conversion maximum value (S1+5) or smaller than the linear conversion minimum value (S1+6). p. 4
107 When the linear conversion is disabled (S1+4 set to 0), the set point (S3) is set to a value larger than 4000. p. 4
200 The current control action (S2+0) differs from that determined at the start of AT. To restart AT, set correct parameters referring to the probable causes listed below: p. 4
201 AT failed to complete normally because the process variable (S4) fluctuated excessively. To restart AT, set the AT sampling period (S1+19) or the input filter coefficient (S1+11) to a larger value. p. 4

Codes and descriptions are taken from the manufacturer’s manual; page numbers link to the PDF. ManualLib is not affiliated with IDEC. Found a mistake? Report an error.