Fujitsu General 410A Error 94: Over current error

Fujitsu General 410A · taken from the manufacturer’s manual, pages cited

Error code94

The inverter compressor has stopped due to overcurrent generation after 10 consecutive attempts. The manual's first action is: “The number of generations is reset if the start-up of the compressor succeeds.”

Model
Fujitsu General 410A
Display shows
Over current error (94)
Type
Error code
Source
Manual p. 11

What 94 means

Over current error p. 11

(Ref. Service Tip #008-Fan Motor Check) p. 6

Common causes

  • Over Current Error – Protection stop by overcurrent generation after inverter compressor start processing completed generated consecutively 10 times. p. 11
  • -Clogged heat exchanger. p. 11
  • -Condenser fan motor defective. p. 11

What to do

  1. The number of generations is reset if the start-up of the compressor succeeds. p. 11
  2. (Ref. Service Tip #008-Fan Motor Check) p. 11

If 94 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Fujitsu General service.

This page summarises what the manufacturer’s manual says about 94; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Fujitsu General. Found a mistake? Report an error.