Active filter / PFC Circuit error code 64 indicates abnormal DC voltage levels or repeated power interruptions. The manual's first action is: “-Check external cause at the indoor or outdoor (voltage drop or noise).”
- Model
- Fujitsu General 410A
- Display shows
- Active filter / PFC Circuit error (64)
- Type
- Error code
- Source
- Manual p. 5
What 64 means
Active filter / PFC Circuit error p. 5
Common causes
- When inverter input DC voltage is higher than 4.25V or lower than 80V. When a momentary power cut off occurred on low voltage. p. 5
- -PFC Circuit Error (9/12RLS3) - When inverter output DC voltage is higher than 415V for over 3 seconds, the compressor stops. If the same operation is repeated 5 times, the compressor stops permanently. p. 5
- -Active Filter Error (15RLS3H, 30RLXEH) - When inverter input DC voltage is higher than 425V or lower than 80V. p. 5
- -Replace Main PCB. p. 5
What to do
- -Check external cause at the indoor or outdoor (voltage drop or noise). p. 5
- -Check connection of connector, loose, erroneous connection. p. 5
- -Ref. Service Tip #010-ACPM Check and/or "ACPM Error" under "Troubleshooting by Error Code" type in Zendesk Help Center. p. 5
If 64 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Fujitsu General service.
This page summarises what the manufacturer’s manual says about 64; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Fujitsu General. Found a mistake? Report an error.