Windows scan indicates there is no signal with the measuring window, or the received signal E is too weak, or there are too frequent small fluctuations and/or improper waveform. The manual's first action is: “Set the action to be taken at the time of burn-out.”
- Model
- Fuji Electric FSC-1/FLD-1/FSD-1
- Display shows
- Windows scan (E2)
- Type
- Error code
- Source
- Manual p. 119
What E2 means
Windows scan p. 119
Common causes
- There is no signal with the measuring window. Therefore the measuring window is being scanned for signal wave. p. 119
- Measurement not possible due to poor strength of Received signal E. p. 119
- Measurement not possible due to too frequent small fluctuations and/or improper waveform. p. 119
- Measurement impossible due to too strong received signal. p. 119
What to do
- Set the action to be taken at the time of burn-out. p. 119
- Check and measure p. 119
- Check if the parameters in Site setting are OK. -Check the sensor mounting condition, and the connection between converter and detector! -Check if the pipe is fully filled with the fluid. p. 119
- Check if the parameters in Site setting are OK. -Check the sensor mounting condition on the pipe surface where the sensors are mounted. -Check if the pipe is fully filled with the fluid. p. 119
- Try to set the transmission voltage lower! -Try to change the mounting method of the detector from Z to V. -Check if the parameters in Site setting are OK. -Check the kind of fluid. -Turn the power off and on! p. 119
Before you service the product, read the safety instructions in the manual p. 6.
If E2 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Fuji Electric service.
This page summarises what the manufacturer’s manual says about E2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Fuji Electric. Found a mistake? Report an error.