ovA on the Delta VFD-VE 系列 is listed in the manual as: During acceleration, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: DC 450 V; 460 V: DC 900 V.. The manual's first action is: “Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the over‑voltage is caused by motor inertia voltage rebound, you can lengthen the deceleration interval or install a braking resistor (optional).”
- Model
- Delta VFD-VE 系列
- Display shows
- ovA
- Type
- Error code
- Source
- Manual p. 235
What ovA means
During acceleration, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: DC 450 V; 460 V: DC 900 V. p. 235
Common causes
- During acceleration, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: DC 450 V; 460 V: DC 900 V. p. 235
What to do
- Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the over‑voltage is caused by motor inertia voltage rebound, you can lengthen the deceleration interval or install a braking resistor (optional). p. 235
Before you service the product, read the safety instructions in the manual p. 72.
If ovA is still not resolved
- Contact local agents for consultation. p. 4 “若有任 何疑虑的地方请连络本公司各地的代理商洽询,我们的专业人员会乐于为您服务。”
This page summarises what the manufacturer’s manual says about ovA; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.