oun on the Delta VFD-VE 系列 is listed in the manual as: During constant‑speed operation, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: 450 V DC; 460 V: 900 V DC.. The manual's first action is: “Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes.”
- Model
- Delta VFD-VE 系列
- Display shows
- oun
- Type
- Error code
- Source
- Manual p. 235
What oun means
During constant‑speed operation, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: 450 V DC; 460 V: 900 V DC. p. 235
Common causes
- During constant‑speed operation, the AC motor drive detected an over‑voltage on the internal high‑voltage DC side. 230 V: 450 V DC; 460 V: 900 V DC. p. 235
What to do
- Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. p. 235
Before you service the product, read the safety instructions in the manual p. 72.
If oun is still not resolved
- Contact local agents for consultation. p. 4 “若有任 何疑虑的地方请连络本公司各地的代理商洽询,我们的专业人员会乐于为您服务。”