Output current exceeds the inverter’s allowable current. The inverter can tolerate 120 % of its rated current for 60 seconds. The manual's first action is: “1. Check whether the motor is overloaded.”
- Model
- Delta VFD-P
- Display shows
- OL
- Type
- Error code
- Source
- Manual p. 70
What OL means
Output current exceeds the inverter’s allowable current. The inverter can tolerate 120 % of its rated current for 60 seconds. p. 70
Common causes
- Output current exceeds the inverter’s allowable current. The inverter can tolerate 120 % of its rated current for 60 seconds. p. 70
What to do
- 1. Check whether the motor is overloaded. p. 70
- 2. Decrease the torque boost setting (parameter 08‑08). p. 70
- 3. Increase the inverter’s output capacity. p. 70
Before you service the product, read the safety instructions in the manual p. 2.
If OL is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.