The OH1 code indicates the AC motor drive detected IGBT temperature too high, exceeding protection limit (1~30 HP: 100°C). The manual's first action is: “Check if ambient temperature is too high; check whether the heat sink has any foreign objects; verify that the fan is rotating; check that the AC motor drive has sufficient ventilation space.”
- Model
- Delta Electronics VFD002DD2 1A
- Display shows
- OH1
- Type
- Error code
- Source
- Manual p. 88
What OH1 means
OH1 IGBT Temperature Too High Detected by AC Motor Drive, Exceeds Protection Limit (1~30 HP: 100°C) p. 106
Common causes
- AC motor drive detected IGBT temperature too high, exceeding protection limit. 1~30 HP: 100°C p. 106
What to do
- Check if ambient temperature is too high; check whether the heat sink has any foreign objects; verify that the fan is rotating; check that the AC motor drive has sufficient ventilation space. p. 106
Before you service the product, read the safety instructions in the manual p. 2.
If OH1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta Electronics service.
This page summarises what the manufacturer’s manual says about OH1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta Electronics. Found a mistake? Report an error.