Fault code7
AI1 LOSS occurs when analog input 1 value falls below A1 FAULT LIMIT (3021). The manual's first action is: “Check for and correct: • Source and connection for analog input. • Parameter settings for A1 FAULT LIMIT (3021) and 3001 AI
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- AI1 LOSS (7)
- Type
- Fault code
- Source
- Manual p. 245
What 7 means
AI1 LOSS p. 261
Common causes
- Analog input 1 loss. Analog input value is less than A1 FAULT LIMIT (3021). p. 261
What to do
- Check for and correct: • Source and connection for analog input. • Parameter settings for A1 FAULT LIMIT (3021) and 3001 AI
p. 261
Before you service the product, read the safety instructions in the manual p. 6.
If 7 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”