PANEL LOSS occurs when panel communication is lost and drive is in local or remote control mode. The manual's first action is: “To correct check: • Communication lines and connection. • Parameter 3002 PANEL COMM ERR. • Parameters in Group 10: START/STOP(DIR) and Group 11: REFERENCE SELECT (if drive operation is REM).”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- PANEL LOSS (10)
- Type
- Fault code
- Source
- Manual p. 245
What 10 means
PANEL LOSS p. 261
Common causes
- Panel communication is lost and either: • Drive is in local control mode (the control panel displays LOC), or • Drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. p. 261
What to do
- To correct check: • Communication lines and connection. • Parameter 3002 PANEL COMM ERR. • Parameters in Group 10: START/STOP(DIR) and Group 11: REFERENCE SELECT (if drive operation is REM). p. 261
Before you service the product, read the safety instructions in the manual p. 6.
If 10 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”
This page summarises what the manufacturer’s manual says about 10; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.