ABB ACS550-01 / ACS550-U1 Error 2: DC OVERVOLT

ACS550-01/U1 drive · taken from the manufacturer’s manual, pages cited

Fault code2

DC OVERVOLT happens when intermediate circuit DC voltage is excessive. The manual's first action is: “Check for and correct: • Static or transient overvoltages in the input power supply. • Insufficient deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2). • Undersized brake chopper (if present). • Verify that overvoltage controller is ON (using parameter 2005).”

Model
ABB ACS550-01 / ACS550-U1
Display shows
DC OVERVOLT (2)
Type
Fault code
Source
Manual p. 245

What 2 means

DC OVERVOLT p. 261

Common causes

  • Intermediate circuit DC voltage is excessive. p. 261

What to do

  1. Check for and correct: • Static or transient overvoltages in the input power supply. • Insufficient deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2). • Undersized brake chopper (if present). • Verify that overvoltage controller is ON (using parameter 2005). p. 261

Before you service the product, read the safety instructions in the manual p. 6.

If 2 is still not resolved

  • contact your local ABB representative for replacement p. 6
    “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
  • For more technical information, contact your local ABB representative. p. 7
    “For more technical information, contact your local ABB representative.”