Fault code2001
2001 means OVERCURRENT, indicating that the output current limit controller is active. The manual's first action is: “Check motor load.”
- Model
- ABB ACS355
- Display shows
- OVERCURRENT (2001)
- Type
- Fault code
- Source
- Manual p. 337
What 2001 means
OVERCURRENT p. 337
Common causes
- Output current limit controller is active. p. 337
What to do
- Check motor load. p. 337
- Check acceleration time (2202 and 2205). p. 337
- Check motor and motor cable (including phasing). p. 337
- Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 359. p. 337
Before you service the product, read the safety instructions in the manual p. 239.
If 2001 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”
This page summarises what the manufacturer’s manual says about 2001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.