ABB ACS355 Error 2001: OVERCURRENT

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code2001

2001 means OVERCURRENT, indicating that the output current limit controller is active. The manual's first action is: “Check motor load.”

Model
ABB ACS355
Display shows
OVERCURRENT (2001)
Type
Fault code
Source
Manual p. 337

What 2001 means

OVERCURRENT p. 337

Common causes

  • Output current limit controller is active. p. 337

What to do

  1. Check motor load. p. 337
  2. Check acceleration time (2202 and 2205). p. 337
  3. Check motor and motor cable (including phasing). p. 337
  4. Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C. See section Derating on page 359. p. 337

Before you service the product, read the safety instructions in the manual p. 239.

If 2001 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 2001; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.