ABB ACS310 Error 0024: OVERSPEED (7310) 0306 bit 7

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0024

Code 0024 means the motor is turning faster than the highest allowed speed due to incorrectly set minimum or maximum speed. The manual's first action is: “Check minimum/maximum frequency settings. Check adequacy of motor braking torque.”

Model
ABB ACS310
Display shows
OVERSPEED (7310) 0306 bit 7 (0024)
Type
Fault code
Source
Manual p. 312

What 0024 means

OVERSPEED (7310) 0306 bit 7 p. 312

Common causes

  • Motor is turning faster than highest allowed speed due to incorrectly set minimum/maximum speed. Operating range limits are set by parameters 2007 MINIMUM FREQ and 2008 MAXIMUM FREQ. p. 312

What to do

  1. Check minimum/maximum frequency settings. Check adequacy of motor braking torque. p. 312

Before you service the product, read the safety instructions in the manual p. 340.

If 0024 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”