ABB ACS310 Error 0022: SUPPLY PHASE (3130) 0306 bit 5

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0022

Code 0022 means intermediate circuit DC voltage is oscillating due to a missing input power line phase or blown fuse, tripping when DC voltage ripple exceeds 14% of nominal DC voltage. The manual's first action is: “Check input power line fuses. Check for input power supply imbalance. Check fault function parameters.”

Model
ABB ACS310
Display shows
SUPPLY PHASE (3130) 0306 bit 5 (0022)
Type
Fault code
Source
Manual p. 312

What 0022 means

SUPPLY PHASE (3130) 0306 bit 5 p. 312

Common causes

  • Intermediate circuit DC voltage is oscillating due to missing input power line phase or blown fuse. Trip occurs when DC voltage ripple exceeds 14% of nominal DC voltage. p. 312

What to do

  1. Check input power line fuses. Check for input power supply imbalance. Check fault function parameters. p. 312

Before you service the product, read the safety instructions in the manual p. 340.

If 0022 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 0022; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.