ABB ACS 160 Error 1: OPERATION FAILED

Low voltage AC drive · taken from the manufacturer’s manual, pages cited

Alarm code1

The OPERATION FAILED code indicates parameter upload or download failed. The manual's first action is: “Software version can be seen from parameter 3301 SOFTWARE VERSION.”

Model
ABB ACS 160
Display shows
OPERATION FAILED (1)
Type
Alarm code
Source
Manual p. 118

What 1 means

OPERATION FAILED p. 118

Common causes

  • Parameter upload or download failed. The software versions of the drives may not be compatible. p. 118
  • Output current is excessive p. 118

What to do

  1. Software version can be seen from parameter 3301 SOFTWARE VERSION. p. 118
  2. • Motor load may be too high • Acceleration time may be too short (parameters 2201 ACCELER TIME 1 and 2203 ACCELER TIME 2) • Motor or motor cable is faulty or connected wrong p. 118

Before you service the product, read the safety instructions in the manual p. 88.

If 1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.