The LOCAL/REMOTE code indicates the control panel function is not allowed in current control mode. The manual's first action is: “• Check air flow and fan operation • Check motor power against unit power”
- Model
- ABB ACS 160
- Display shows
- LOCAL/REMOTE (3)
- Type
- Fault code
- Source
- Manual p. 118
What 3 means
LOCAL/REMOTE p. 120
Common causes
- Control panel function is not allowed in current control mode (local or remote). Control mode is local when LOC is displayed and remote mode when REM is displayed on the control panel. p. 120
- ACS 160 heatsink temperature is excessive. Temperature trip limit is 105 °C p. 120
What to do
- • Check air flow and fan operation • Check motor power against unit power p. 120
Before you service the product, read the safety instructions in the manual p. 88.
If 3 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.