STO1 LOST (0x8182) means safe torque off function is active, i.e. safety circuit signal 1 connected between XSTO:1 and XSTO:3 is lost. The manual's first action is: “Check safety circuit connections. For more information, see appropriate drive hardware manual, description of parameter 30.07 (page 196), and Application guide - Safe torque off function for ACSM1, ACS850 and ACQ810 drives (3AFE68929814 [English]).”
- Model
- ABB ACQ810
- Display shows
- STO1 LOST (0x8182) (0021)
- Type
- Fault code
- Source
- Manual p. 323
What 0021 means
STO1 LOST (0x8182) p. 323
Common causes
- Safe torque off function is active, i.e. safety circuit signal 1 connected between XSTO:1 and XSTO:3 is lost. p. 323
What to do
- Check safety circuit connections. For more information, see appropriate drive hardware manual, description of parameter 30.07 (page 196), and Application guide - Safe torque off function for ACSM1, ACS850 and ACQ810 drives (3AFE68929814 [English]). p. 323
Before you service the product, read the safety instructions in the manual p. 195.
If 0021 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact ABB service.
This page summarises what the manufacturer’s manual says about 0021; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.